Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Preslab
| Date |
Description |
Inspector |
Results |
Comments |
| 03/10/2025 |
COT - RSBU - Preslab |
|
Re-inspection required |
3/10/25: footers not per plan (detail B1), footers not at proper depth, reinforcement requires 3" clearance from earth, post footings not per plan, reinforcement overlap requires 24" min, gray water must terminate 24" above finish grade. |
| 03/12/2025 |
COT - RSBU - Preslab |
|
Passed |
3/12/25 corrections made |