Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date |
Description |
Inspector |
Results |
Comments |
| 04/24/2025 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Re-inspection required |
4/24/25:Properly seal all penetrations through vapor barrier and top plate, 3” ABS for future solar missing at water heater, truss gusset plates missing/damaged in garage, EV receptacle missing in garage, framing not per plan, smoke alarm missing outside of bedroom 4, FHA plate required at kitchen exhaust duct, seal pipes in slab at kitchen, Bedroom 1 is calling for 12/2 wire for receptacles (revise plan), missing circuits at panel (not per plan), support flex at bedroom 1 and bathroom, blocking required on 4-gang boxes, Attic access requires 30” of head room clearance( flex running through attic access), condensate drain must be secured, nail plate required in north bathroom, A/C register missing at entry, Attic vent missing, lath incomplete. |
| 04/25/2025 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Passed |
|