Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 2/26/25: RSP4 at south wall near entry must be properly fastened, At sill plates greater than 12" (2) Anchor bolts required, Anchor bolt required 12" from edge of sill plate, At shear wall 11 and greater 3"x3" washer plates required. STOPPED INSPECTION MORE ITEMS MAY BE ADDED
02/28/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required MAY BE ADDED

28 FEB 25
1. Shot pins are missing in interiors walls, within 6" of every edge.
2. Truss A1E is missing lateral bracing, just south of first brace.
03/03/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 3 MAR 25
ALL CORRECTIONS HAVE BEEN MADE.