Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSPL - Plumbing Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2026 | COT - RSPL - Plumbing Final | Re-inspection required | 7/6/26: PT tag at hose-bib required, 3" clearance at condenser required from grade, properly secure disconnect box at condenser, condenser unit is being over amped 30 amp max, please mark which heat kit is installed at air handler on tag to verify correct amperage, properly support flex in attic 4' o.c max, receptacle cover plate required at kitchen island, exhaust fan in attic not functioning and cover must be appropriately installed, porch/foyer circuit cut power to laundry (lighting and exhaust) and to garage lighting. | |
| 07/29/2026 | COT - RSPL - Plumbing Final | Passed | 07/29/2026 All corrections made. Conditions satisfied as well. |