Inspection History: COT - RSME - Mechanical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2026 | COT - RSME - Mechanical Final | Re-inspection required | 7/6/26: PT tag at hose-bib required, 3" clearance at condenser required from grade, properly secure disconnect box at condenser, condenser unit is being over amped 30 amp max, please mark which heat kit is installed at air handler on tag to verify correct amperage, properly support flex in attic 4' o.c max, receptacle cover plate required at kitchen island, exhaust fan in attic not functioning and cover must be appropriately installed, porch/foyer circuit cut power to laundry (lighting and exhaust) and to garage lighting. | |
| 07/29/2026 | COT - RSME - Mechanical Final | Passed | 07/29/2026 All corrections made. Conditions satisfied as well. |