Permit: TC-MDP-0124-00074

Parcel: 136130750

Inspection Status: Not Ready

Inspection History: COT - RSBU - Interior Shear Bracing 

Date Description Inspector Results Comments
06/30/2025 COT - RSBU - Interior Shear Bracing  Not Ready not ready
07/01/2025 COT - RSBU - Interior Shear Bracing  Re-inspection required 7/1/25
1. Bottom of stairs by landing, wall is bending out and fasteners are over penetrated and spacing is not per plan 7" o.c. Fasteners must be no closer than 3/8" from edges.
2. Garage both walls must be replaced, over penetrations and spacing not per plan.
3. Dining are wall damaged drywall and spacing not per plan.
4. Master closet wall 1" gap in seams
5. Damaged wall in Master bedroom, needs to be replaced.
07/03/2025 COT - RSBU - Interior Shear Bracing  Passed Passed 7/3/25
08/01/2025 COT - RSBU - Interior Shear Bracing  Passed 8/01/25
Passed by D.C on 7/3/25.