Inspection Status: Not Ready
Inspection History: COT - RSBU - Interior Shear Bracing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2025 | COT - RSBU - Interior Shear Bracing | Not Ready | not ready | |
| 07/01/2025 | COT - RSBU - Interior Shear Bracing | Re-inspection required | 7/1/25 1. Bottom of stairs by landing, wall is bending out and fasteners are over penetrated and spacing is not per plan 7" o.c. Fasteners must be no closer than 3/8" from edges. 2. Garage both walls must be replaced, over penetrations and spacing not per plan. 3. Dining are wall damaged drywall and spacing not per plan. 4. Master closet wall 1" gap in seams 5. Damaged wall in Master bedroom, needs to be replaced. |
|
| 07/03/2025 | COT - RSBU - Interior Shear Bracing | Passed | Passed 7/3/25 | |
| 08/01/2025 | COT - RSBU - Interior Shear Bracing | Passed | 8/01/25 Passed by D.C on 7/3/25. |