Permit: TC-FBB-0524-00109

Parcel: 140241270


Addresses:

1211 E GINTER RD

Inspection Status: Re-inspection required

Inspection History: BULD - Electrical Clearance

Date Description Inspector Results Comments
08/16/2024 BULD - Electrical Clearance Re-inspection required 8/16/24: Equipment grounding conductor shall be identified by a continuous green color or continuous green color with one or more yellow stripes on insulation (E3407.2), raceway exposed to physical damage must be in schedule 80 PVC (E3803.3), Feeders that have damaged insulation have to be either repaired or replaced, properly secure ground to utility pole.
08/20/2024 BULD - Electrical Clearance Passed 8/16/24: Equipment grounding conductor shall be identified by a continuous green color or continuous green color with one or more yellow stripes on insulation (E3407.2), raceway exposed to physical damage must be in schedule 80 PVC (E3803.3), Feeders that have damaged insulation have to be either repaired or replaced, properly secure ground to utility pole.
8/20/24: INCR TEP CLEARANCE AT 1211 E GINTER RD