Inspection Status: Partial Pass
Inspection History: COT - LCEL - Electrical Intermediate
| Date |
Description |
Inspector |
Results |
Comments |
| 09/16/2026 |
COT - LCEL - Electrical Intermediate |
|
Partial Pass |
9/16/26: in wall electrical (interior/exterior) and above ceiling area 101 approved. Okay to continue with construction at progress areas. |
| 10/05/2026 |
COT - LCEL - Electrical Intermediate |
|
Re-inspection required |
10/5/26: add supports to electrical conduits 4' from grade at study area along east wall, fire caulk penetrations throughout. |
| 10/13/2026 |
COT - LCEL - Electrical Intermediate |
|
Partial Pass |
10/13/26: 2-4" & 1-2" secondary Schedule 40 electrical conduits from SES towards new build. Conduit runs south to north-okay to backfill approximately 120' of open trench using shading materials. |
|
COT - LCEL - Electrical Intermediate |
|
Scheduled |
|