Permit: TC-COM-1225-02340

Parcel: 11918034B


Addresses:

3500 S 12TH AV

Inspection Status: Partial Pass

Inspection History: COT - LCEL - Electrical Intermediate

Date Description Inspector Results Comments
09/16/2026 COT - LCEL - Electrical Intermediate Partial Pass 9/16/26: in wall electrical (interior/exterior) and above ceiling area 101 approved. Okay to continue with construction at progress areas.
10/05/2026 COT - LCEL - Electrical Intermediate Re-inspection required 10/5/26: add supports to electrical conduits 4' from grade at study area along east wall, fire caulk penetrations throughout.
10/13/2026 COT - LCEL - Electrical Intermediate Partial Pass 10/13/26: 2-4" & 1-2" secondary Schedule 40 electrical conduits from SES towards new build. Conduit runs south to north-okay to backfill approximately 120' of open trench using shading materials.
COT - LCEL - Electrical Intermediate Scheduled