Inspection History Details
Inspection Status: Requested
Inspection History: COT - LCEL - Electrical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| COT - LCEL - Electrical Final | Requested | |||
| COT - LCEL - Electrical Final | Partial Pass | 6-2-26: electrical & mechanical finals at room's 413, 412, 315, 314, 313, 312 approved. | ||
| 08/10/2026 | COT - LCEL - Electrical Final | Canceled | ||
| 08/11/2026 | COT - LCEL - Electrical Final | Partial Pass | 8-11-26: Electrical Final at room's IDF3, 1005, 812A, 813, 815, 814, 816, 810, 809, 808, 806, 805, 804, 803, 802, 801 approved. Room 807-install GFCI receptacle at wall within 6' of water ( refrigerator receptacle.) |
|
| 08/19/2026 | COT - LCEL - Electrical Final | Re-inspection required | 8-19-26: 807-correction made, 905, 903, 902, 901, 910, 909, 908, 907, 906, Open office areas & 701 approved. Provide updated panel schedules for LF2A & LF1A & submit to the city. Label above ceiling junction boxes at Facilities room & schedule electrical final for pending areas and to verify corrections where required. Note: Schedule all other final inspections such as engineering/plumbing/mechanical and submit all required condition reports to the city for review & approval. |