Permit: TC-COM-1225-02297

Parcel: 140290290


Addresses:

3301 E GLOBAL LP

Inspection Status: Requested

Inspection History: COT - LCEL - Electrical Final 

Date Description Inspector Results Comments
COT - LCEL - Electrical Final  Requested
COT - LCEL - Electrical Final  Partial Pass 6-2-26: electrical & mechanical finals at room's 413, 412, 315, 314, 313, 312 approved.
08/10/2026 COT - LCEL - Electrical Final  Canceled
08/11/2026 COT - LCEL - Electrical Final  Partial Pass 8-11-26: Electrical Final at room's IDF3, 1005, 812A, 813, 815, 814, 816, 810, 809, 808, 806, 805, 804, 803, 802, 801 approved.
Room 807-install GFCI receptacle at wall within 6' of water ( refrigerator receptacle.)
08/19/2026 COT - LCEL - Electrical Final  Re-inspection required 8-19-26: 807-correction made, 905, 903, 902, 901, 910, 909, 908, 907, 906, Open office areas & 701 approved. Provide updated panel schedules for LF2A & LF1A & submit to the city. Label above ceiling junction boxes at Facilities room & schedule electrical final for pending areas and to verify corrections where required.
Note: Schedule all other final inspections such as engineering/plumbing/mechanical and submit all required condition reports to the city for review & approval.