Inspection Status: Canceled
Inspection History: COT - LCEL - Electrical Intermediate
| Date |
Description |
Inspector |
Results |
Comments |
| 05/27/2026 |
COT - LCEL - Electrical Intermediate |
|
Canceled |
5-27-26: canceled by contractor. |
| 08/31/2026 |
COT - LCEL - Electrical Intermediate |
|
Re-inspection required |
8-31-26: in wall rough electrical-missing low in wall electrical receptacles at west wall, add pigtails to ground screws to in wall receptacles throughout, provide vertical supports for rmc at 10' intervals and within 12" of a receptacle box. We will look at the above required corrections at intermediates. |