Permit: TC-COM-1225-02185

Parcel: 14118652A


Addresses:

10100 E OLD VAIL RD

Inspection Status: Partial Pass

Inspection History: COT - LCBU - Framing

Date Description Inspector Results Comments
06/25/2026 COT - LCBU - Framing Partial Pass 6-25-26: partial pass- install washers at all hold downs, missing lsta36 between header & jack studs-loop over header to opposite side-see S001 Detail 7. Need to verify all A35's per same detail. Missing edge nailing at decking/parapet at several areas. Reschedule inspection at your convenience.
06/26/2026 COT - LCBU - Framing Partial Pass 6-26-26: framing for shell approved. Okay to continue with construction at progress areas.