Inspection Status: Canceled
Inspection History: BULD - Electrical Clearance
| Date |
Description |
Inspector |
Results |
Comments |
| 03/27/2026 |
BULD - Electrical Clearance |
|
Canceled |
3-27-26: canceled by contractor. |
| 04/22/2026 |
BULD - Electrical Clearance |
|
Re-inspection required |
4-22-26: Install metallic addressing labels for each unit, provide plastic bushings to protect awg wires (feeders) at sub panels, install metallic addressing labels at each subpanel. Make sure bonding/grounding is complete per SES details. Provide torque specifications and submit report as an attachment to the city for review. |
| 04/24/2026 |
BULD - Electrical Clearance |
|
Partial Pass |
4-24-26: Okay to meter SES1 to energize Panel 1A. |
| 04/27/2026 |
BULD - Electrical Clearance |
|
Canceled |
4-27-26: canceled by contractor. |