Inspection Status: Partial Pass
Inspection History: COT - HCBU - Excavation/Rebar/Zoning
| Date |
Description |
Inspector |
Results |
Comments |
| 04/01/2026 |
COT - HCBU - Excavation/Rebar/Zoning |
|
Partial Pass |
4-1-26: excavation/reinforcement for pergola footers at courtyard verified per S33.1 detail 12. Okay for concrete placement. |
| 06/27/2025 |
COT - HCBU - Excavation/Rebar/Zoning |
|
Partial Pass |
6/27/25: Third party inspector passed reinforcement for lower floor slab and sump pit for building elevator Detail S3.02/4, elevator pit concrete walls reinforced per plan. |
| 08/07/2025 |
COT - HCBU - Excavation/Rebar/Zoning |
|
Partial Pass |
8/7/2025 area B okay for concrete placement. |
| 08/25/2025 |
COT - HCBU - Excavation/Rebar/Zoning |
|
Re-inspection required |
8-25-25: not ready-missing reinforcement at several areas. SEE S1.0A-Details 3 & 2. |
| 08/28/2025 |
COT - HCBU - Excavation/Rebar/Zoning |
|
Partial Pass |
8.28.25: Area A ok for concrete placement. |
| 09/25/2025 |
COT - HCBU - Excavation/Rebar/Zoning |
|
Canceled |
9-25-25: canceled by contractor. |
| 09/29/2025 |
COT - HCBU - Excavation/Rebar/Zoning |
|
Partial Pass |
9-29-25: reinforcement at elevator equipment room verified at #5 -24" o.c.. lift at 6'- 3rd party inspection report presented. |
| 09/30/2025 |
COT - HCBU - Excavation/Rebar/Zoning |
|
Partial Pass |
9-30-25: top out at elevator equipment room at 9'-okay to grout. |