Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/24/2026 | COT - HCEL - Electrical Final | Partial Pass | 3-24-26: B102 approved. | |
| 03/31/2026 | COT - HCEL - Electrical Final | Re-inspection required | 3-31-26: install panel label and a label for disconnect, remove covers from smoke detectors, missing restroom door-required to test pounds of pressure, missing water heater door. C105-install panel label and a label for disconnect, remove covers from smoke detectors, secure conduit/whip at water heater (add another clamp), missing pressure relief valve. Note: a p-trap test for showers required. This was documented in previous notes. |
|
| 04/01/2026 | COT - HCEL - Electrical Final | Partial Pass | 4/1/26: All issues listed above corrected. Pending electrical corrections at kitchen circuits per A117.1, pending correction at HVAC refrigerant lines and electrical whips. Revision required for HVAC system upsized to 2 ton (plans and Manual J require 1.5Ton) | |