Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - HCEL - Outdoor Lighting
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2026 | COT - HCEL - Outdoor Lighting | Re-inspection required | 11/10/26: total of 6 common area restrooms-add a total of 4 cover plates to exposed low voltage abandoned in wall boxes. 2-community areas at 1st & 2nd floor-approved. Add hammer arrestees at 1st floor laundry room-verified gfci's at laundry rooms. Pending conditions and hvac revision. Have engineer submit revision to the city for review & approval. Replace all exterior receptacles to "weather resistant" gfci's and add bubble covers. Note: none of the exterior HVAC units nor exterior electrical have been inspected. When ready schedule inspections. |