Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Progress
| Date |
Description |
Inspector |
Results |
Comments |
| 03/13/2026 |
COT - HCEL - Electrical Progress |
|
Partial Pass |
3-13-26: in wall electrical approved-okay to install first layer of 5/8" drywall at progress areas. Schedule a drywall screw inspection prior to tape & texture. |
| 03/19/2026 |
COT - HCEL - Electrical Progress |
|
Not Ready |
3/19/2026 not ready. Room #c119. Extend electrical boxes so that when it's time for drywall they'll be flushed. Fire caulk all penetrations above ceiling into firewalls. No bundling more than 4 wires per hole. Smoke detectors not set in place along with kitchen receptacles. Secure loos wires vertically. |