Permit: TC-COM-1224-02366

Parcel: 137073210


Addresses:

4945 S LIBERTY AV

Inspection Status: Partial Pass

Inspection History: COT - HCEL - Electrical Progress  

Date Description Inspector Results Comments
03/13/2026 COT - HCEL - Electrical Progress   Partial Pass 3-13-26: in wall electrical approved-okay to install first layer of 5/8" drywall at progress areas. Schedule a drywall screw inspection prior to tape & texture.
03/19/2026 COT - HCEL - Electrical Progress   Not Ready 3/19/2026 not ready. Room #c119. Extend electrical boxes so that when it's time for drywall they'll be flushed. Fire caulk all penetrations above ceiling into firewalls. No bundling more than 4 wires per hole. Smoke detectors not set in place along with kitchen receptacles. Secure loos wires vertically.
05/11/2026 COT - HCEL - Electrical Progress   Partial Pass 5-11-26: mechanical/electrical/plumbing at the interior of unit's B114, B115, B116, B213, B214, B215, B216 approved for a Level 4 TCO.
NOTE: exterior condensers/labeling of disconnects/proper installation of refrigerant lines and sealing at disconnects must still be inspected. Waiting on RFI approval and contractor to schedule inspections.
05/13/2026 COT - HCEL - Electrical Progress   Partial Pass 5-13-26: MEP's together with mechanical, electrical, and plumbing finals for Unit's B110 & B112 approved. Exterior HVAC will be inspected at a later date.