Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Inspection Status: Re-inspection required

Inspection History: COT - LCPL - Gas Pressure Test 

Date Description Inspector Results Comments
11/16/2026 COT - LCPL - Gas Pressure Test  Re-inspection required 11/16/2026
Steel pipe buried in ground needs factory-applied corrosion protection or anodeless risers on both ends. The use of PE pipe suffices with yellow 14AWG tracer wire for the long run. 2024 IRC G2425.11.2 code reference.
11/17/2026 COT - LCPL - Gas Pressure Test  Passed