Permit: TC-COM-1125-02102

Parcel: 141186020


Addresses:

10023 E OLD VAIL RD

Inspection Status: Partial Pass

Inspection History: COT - HCEL - Electrical Progress  

Date Description Inspector Results Comments
03/02/2026 COT - HCEL - Electrical Progress   Partial Pass 3/2/26: UFER approved
03/06/2026 COT - HCEL - Electrical Progress   Partial Pass 3-6-26: verified trench depth at approximately 3' for 5-2 1/2" & 1-1 1/2" Schedule 40 conduits intended for future panels. Okay to backfill approximately 80' of open trench.
06/08/2026 COT - HCEL - Electrical Progress   Partial Pass 6-8-26: verified 2-grounding rods with 3/0 copper for SES.
06/23/2026 COT - HCEL - Electrical Progress   Canceled 6-23-26: canceled.
06/24/2026 COT - HCEL - Electrical Progress   Partial Pass 6-24-26: partial pass for in wall rough electrical. A few receptacles are missing grounding nut and pigtails. Fire foam all penetrations at top plates-Fire foam/ grounding nuts/pigtails will be inspected at upcoming inspections.
06/30/2026 COT - HCEL - Electrical Progress   Re-inspection required 6-30-26: fire caulk around Mc- cabling at end of suite walls. Missing anchor bolts/plate together with a 6" clearance at base of light pole cage located south of building 3.
07/02/2026 COT - HCEL - Electrical Progress   Partial Pass 7-2-26: electrical penetrations at top plates fire foamed.
07/07/2026 COT - HCEL - Electrical Progress   Partial Pass