Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Progress
| Date |
Description |
Inspector |
Results |
Comments |
| 03/02/2026 |
COT - HCEL - Electrical Progress |
|
Partial Pass |
3/2/26: UFER approved |
| 03/06/2026 |
COT - HCEL - Electrical Progress |
|
Partial Pass |
3-6-26: verified trench depth at approximately 3' for 5-2 1/2" & 1-1 1/2" Schedule 40 conduits intended for future panels. Okay to backfill approximately 80' of open trench. |
| 06/08/2026 |
COT - HCEL - Electrical Progress |
|
Partial Pass |
6-8-26: verified 2-grounding rods with 3/0 copper for SES. |
| 06/23/2026 |
COT - HCEL - Electrical Progress |
|
Canceled |
6-23-26: canceled. |
| 06/24/2026 |
COT - HCEL - Electrical Progress |
|
Partial Pass |
6-24-26: partial pass for in wall rough electrical. A few receptacles are missing grounding nut and pigtails. Fire foam all penetrations at top plates-Fire foam/ grounding nuts/pigtails will be inspected at upcoming inspections. |
| 06/30/2026 |
COT - HCEL - Electrical Progress |
|
Re-inspection required |
6-30-26: fire caulk around Mc- cabling at end of suite walls. Missing anchor bolts/plate together with a 6" clearance at base of light pole cage located south of building 3. |
| 07/02/2026 |
COT - HCEL - Electrical Progress |
|
Partial Pass |
7-2-26: electrical penetrations at top plates fire foamed. |
| 07/07/2026 |
COT - HCEL - Electrical Progress |
|
Partial Pass |
|