Inspection Status: Re-inspection required
Inspection History: COT - HCBU - Building Final
| Date |
Description |
Inspector |
Results |
Comments |
| 09/15/2026 |
COT - HCBU - Building Final |
|
Re-inspection required |
9/15/26: label above ceiling junction boxes, label disconnects, label panel & provide panel schedules, weather resistant gfci receptacles required at rooftop, secure whips within 12" of disconnects. |
| 09/16/2026 |
COT - HCBU - Building Final |
|
Partial Pass |
9/16/26: partial pass pending outstanding inspections-Please schedule all remaining. |
| 09/17/2026 |
COT - HCBU - Building Final |
|
Partial Pass |
9/17/26: partial pass pending gas meter installation. |
| 09/23/2026 |
COT - HCBU - Building Final |
|
Passed |
|