Permit: TC-COM-1125-02102

Parcel: 141186020


Addresses:

10023 E OLD VAIL RD

Inspection Status: Re-inspection required

Inspection History: COT - HCBU - Building Final 

Date Description Inspector Results Comments
09/15/2026 COT - HCBU - Building Final  Re-inspection required 9/15/26: label above ceiling junction boxes, label disconnects, label panel & provide panel schedules, weather resistant gfci receptacles required at rooftop, secure whips within 12" of disconnects.
09/16/2026 COT - HCBU - Building Final  Partial Pass 9/16/26: partial pass pending outstanding inspections-Please schedule all remaining.
09/17/2026 COT - HCBU - Building Final  Partial Pass 9/17/26: partial pass pending gas meter installation.
09/23/2026 COT - HCBU - Building Final  Passed