| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/06/2025 | COT - LCPL - Plumbing Final | Re-inspection required | 8-6-25: missing hammer arrestors at refrigerator & water closets, extend PTR copper line on water heater to mop sink, wrap hot water copper line on water heater with R3 insulation. Note: only inspected TI areas. Existing portions of location not inspected as of yet. |
|
| 08/27/2025 | COT - LCPL - Plumbing Final | Re-inspection required | 8-27-25: pending conditions, required corrections to include: wrapping of hot piping on water heater, RFI for HVAC & RFI for receptacle relocation in office area, adjusting all interior /exit doors to open at 5 pounds of pressure, missing junction box lid at electrical room above ceiling,firefoam any vertical /horizontal penetration where piping/conduits extend through to another space. Existing electrical panels not in use must be "gutted" to the possible unlawful use at a later date and must be clearly labeled "panel not in use." | |
| 09/02/2025 | COT - LCPL - Plumbing Final | Passed | 9-2-25: plumbing final approved. |