Permit: TC-COM-1124-02266

Parcel: 140420190


Addresses:

2701 E ELVIRA RD

Inspection Status: Re-inspection required

Inspection History: COT - LCEL - Electrical Final 

Date Description Inspector Results Comments
08/27/2025 COT - LCEL - Electrical Final  Re-inspection required 8-27-25: pending conditions, required corrections to include: wrapping of hot piping on water heater, RFI for HVAC & RFI for receptacle relocation in office area, adjusting all interior /exit doors to open at 5 pounds of pressure, missing junction box lid at electrical room above ceiling,firefoam any vertical /horizontal penetration where piping/conduits extend through to another space. Existing electrical panels not in use must be "gutted" to the possible unlawful use at a later date and must be clearly labeled "panel not in use."
09/02/2025 COT - LCEL - Electrical Final  Passed 9-2-25: electrical final approved.