Inspection Status: Partial Pass
Inspection History: COT - LCPL - Rough Soil
| Date |
Description |
Inspector |
Results |
Comments |
| 04/01/2025 |
COT - LCPL - Rough Soil |
|
Partial Pass |
4-1-25, underground plumbing inside of building verified under test and per approved plans. PEX at 60psi and sewer line in same trench-okay to backfill approximately 300' with shading materials. Maintain a 12" clearance between PEX and sewer. Also, have architect/engineer submit a revision for installation of additional backflow preventer. |
| 05/01/2025 |
COT - LCPL - Rough Soil |
|
Re-inspection required |
5-1-25, pending RFI for additional backflow preventer from architect/engineer. Submit to the city for review and approval. |
| 10/10/2025 |
COT - LCPL - Rough Soil |
|
Passed |
|