Permit: TC-COM-1124-02162

Parcel: 140420190


Addresses:

2721 E ELVIRA RD

Inspection Status: Re-inspection required

Inspection History: COT - HCBU - CofO

Date Description Inspector Results Comments
08/27/2025 COT - HCBU - CofO Re-inspection required 8-27-25: pending conditions, required corrections to include: wrapping of hot piping on water heater, RFI for HVAC & RFI for receptacle relocation in office area, adjusting all interior /exit doors to open at 5 pounds of pressure, secure mc cable & fire foam penetration above electrical HV1 panel and at any horizontal penetration where piping/conduits extend through to another space. Existing electrical panels not in use must be "gutted" to the possible unlawful use at a later date and must be clearly labeled "panel not in use."
09/02/2025 COT - HCBU - CofO Re-inspection required 9-2-25: secure mc cable & fire foam penetration above electrical HV1 panel and at any horizontal penetration where piping/conduits extend through to another space. Existing electrical panels not in use must be clearly labeled "panel not in use" and add blanks to open knock outs at panels not being used. Pending electrical & HVAC RFI.
09/05/2025 COT - HCBU - CofO Partial Pass 9-5-25: partial pass pending Electrical & HVAC RFI
Okay for Level 4 TCO.
09/09/2025 COT - HCBU - CofO Partial Pass 9-9-25: building final approved. Okay for Level 4 TCO-See pending conditions.
09/10/2025 COT - HCBU - CofO Passed