Permit: TC-COM-1124-02162

Parcel: 140420190


Addresses:

2721 E ELVIRA RD

Inspection Status: Re-inspection required

Inspection History: COT - HCPL - Plumbing Intermediate 

Date Description Inspector Results Comments
05/19/2025 COT - HCPL - Plumbing Intermediate  Re-inspection required 5/19/25: (2)supports required at vertical runs at DVW, leak at test cap, (1) support required at domestic water at east bathroom in wall. Plumbing under test.
08/27/2025 COT - HCPL - Plumbing Intermediate  Re-inspection required 8-27-25: pending conditions, required corrections to include: wrapping of hot piping on water heater, RFI for HVAC & RFI for receptacle relocation in office area, adjusting all interior /exit doors to open at 5 pounds of pressure, secure mc cable & fire foam penetration above electrical HV1 panel and at any horizontal penetration where piping/conduits extend through to another space. Existing electrical panels not in use must be "gutted" to the possible unlawful use at a later date and must be clearly labeled "panel not in use."
09/02/2025 COT - HCPL - Plumbing Intermediate  Passed 9-2-25: approved.