Permit: TC-COM-1123-02689

Parcel: 136048100

Inspection Status: Passed

Inspection History: BULD - Electrical Clearance

Date Description Inspector Results Comments
06/26/2026 BULD - Electrical Clearance Passed passed clearance eco
08/05/2026 BULD - Electrical Clearance Passed TEP CLEARANCE: ECO
08/26/2026 BULD - Electrical Clearance Re-inspection required 8/26/26: Bond/bushings missing throughout at raceways, multiple raceways not properly installed/secured, raceways must be properly secured at unistrut, multiple conductors are improperly secured at lugs and are undersized for lugs, torque report required,ground wire must be appropriately identified, revision required for electrical equipment (not per plans), emt at grade and below must be protected from corrosion. Conductors must be appropriately sized, fuses missing at disconnect box, conductors nicked where sheathing was removed.
08/31/2026 BULD - Electrical Clearance Re-inspection required 8/31/26: Conductors must be properly torqued to spec (torque sheet required at time of inspection) (conductors are loose at disconnect)(bond Cushing must be properly secured and attached at raceways). All other items have been addressed from previous inspection.
09/09/2026 BULD - Electrical Clearance Passed 9/9/26: TEP ECO CLEARANCE APPROVED FOR 8815 E GOLF LINKS RD