Inspection Status: Passed
Inspection History: BULD - Electrical Clearance
| Date |
Description |
Inspector |
Results |
Comments |
| 06/26/2026 |
BULD - Electrical Clearance |
|
Passed |
passed clearance eco |
| 08/05/2026 |
BULD - Electrical Clearance |
|
Passed |
TEP CLEARANCE: ECO |
| 08/26/2026 |
BULD - Electrical Clearance |
|
Re-inspection required |
8/26/26: Bond/bushings missing throughout at raceways, multiple raceways not properly installed/secured, raceways must be properly secured at unistrut, multiple conductors are improperly secured at lugs and are undersized for lugs, torque report required,ground wire must be appropriately identified, revision required for electrical equipment (not per plans), emt at grade and below must be protected from corrosion. Conductors must be appropriately sized, fuses missing at disconnect box, conductors nicked where sheathing was removed. |
| 08/31/2026 |
BULD - Electrical Clearance |
|
Re-inspection required |
8/31/26: Conductors must be properly torqued to spec (torque sheet required at time of inspection) (conductors are loose at disconnect)(bond Cushing must be properly secured and attached at raceways). All other items have been addressed from previous inspection. |
| 09/09/2026 |
BULD - Electrical Clearance |
|
Passed |
9/9/26: TEP ECO CLEARANCE APPROVED FOR 8815 E GOLF LINKS RD |