Inspection Status: Partial Pass
Inspection History: COT - FCON - Sprinkler - Final
Permit Number - TC-COM-1122-00039
Inspection Description - COT - FCON - Sprinkler - Final
Inspection Status - Partial Pass
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2023 | COT - FCON - Sprinkler - Final | Partial Pass | North and east patio 5-6 heads are blocked by electrical conduit or lighting fixtures, Roll up door on north side of restaurant no coverage under door when open, bag covering head above bar. | |
08/15/2023 | COT - FCON - Sprinkler - Final | Partial Pass | Building #1 sprinkler coverage needs to be added under the (4) roll-up doors on east wall. | |
08/22/2023 | COT - FCON - Sprinkler - Final | Passed |