Permit: TC-COM-1024-02027

Parcel: 11506107B


Addresses:

1910 N STONE AV

Inspection Status: Not Ready

Inspection History: COT - HCPL - Plumbing Final 

Date Description Inspector Results Comments
10/02/2026 COT - HCPL - Plumbing Final  Not Ready
10/14/2026 COT - HCPL - Plumbing Final  Not Ready
10/19/2026 COT - HCPL - Plumbing Final  Partial Pass
10/20/2026 COT - HCPL - Plumbing Final  Not Ready 10/20/2026 unit 111 provide receptacle right of range. Stopped inspection due to super kicking me off site.
10/21/2026 COT - HCPL - Plumbing Final  Re-inspection required 10/21/26: Walked units 110,111(ADA),112,113,115:
items found
1) GFCI/AFCI required at Microwave receptacles Per NEC 210.8 & 210.12
2) Insulation required at water heater per 2018 IECC C404.4
3)Kitchen Exhaust shall be installed with ducts that have smooth inner walls per 2018 IMC 505.3
4)Condensate drain penetration at plenum must be sealed at all mechanical closets 2018 IMC 302.2
5)ADA units shall comply with all requirements of the A117.1
*Grab bar required at roll in shower per 608.3.2.3
*reach range for receptacles and Switches at counter top exceed the 25" maximum reach per A117.1 308.2.2
* piping under sinks shall be protected per A117.1 606.6 (cords are included, please secure out the way)
6)properly install lock out at water heater circuit in panel,
10/22/2026 COT - HCPL - Plumbing Final  Re-inspection required 10/22/26: 1910 N Stone,

2nd floor MEP finals Rooms

232: seal penetration for condensate drain at mechanical closet, seal penetration at ceiling for kitchen hood.
233:counter top recp spacing, 2 kitchen circuit required,secure mc in mechanical closet, mark air handler heat kit, seal penetrations in mechanical closet into plenum, seal penetration at ceiling for kitchen exhaust,bedroom recp spacing,
230: spacing at kitchen counter,seal penetrations in mechanical closet into plenum, seal penetration at ceiling for kitchen exhaust
231:recp spacing at kitchen,mc clamp at mechanical closet,seal penetrations in mechanical closet into plenum, seal penetration at ceiling for kitchen exhaust
228: recp at kitchen spacing/missing,clamp mechanical room,seal penetrations in mechanical closet into plenum, seal penetration at ceiling for kitchen exhaust
226:fire caulk around mechanical kitchen exhaust.seal penetrations in mechanical closet into plenum.
10/26/2026 COT - HCPL - Plumbing Final  Re-inspection required
10/28/2026 COT - HCPL - Plumbing Final  Not Ready