Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Underground
Permit Number - TC-COM-1024-02027
Inspection Description - COT - HCEL - Electrical Underground
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2025 | COT - HCEL - Electrical Underground | Partial Pass | SES 3” conduits (10 each), approximately 35’. OK to cover progress area. | |
| 11/20/2025 | COT - HCEL - Electrical Underground | Partial Pass | X1 4” schedule 40 @ 7.5’ - 5’ depth. Feeding prprimaries. Just past HCS line. 90 heading north to transformer location. X10 4” schedule 40 @ 7.5’ - 5’ depth feeding secondaries tied into building. Okay to backfill all progress areas. Shading material required. Ensure tape is in place after first lift of compaction. 11/20/2025 |