Inspection Status: Not Ready
Inspection History: COT - HCME - Mechanical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 07/03/2024 |
COT - HCME - Mechanical Final |
|
Not Ready |
|
| 08/15/2024 |
COT - HCME - Mechanical Final |
|
Not Ready |
|
| 08/19/2024 |
COT - HCME - Mechanical Final |
|
Re-inspection required |
8/19/24: (Office area inspection) Grab Bars not installed at time of inspection, coat hangers not per ADA requirements, properly mount instantaneous water heaters at restrooms, GFCI receptacles required under Lavatories, panel schedules must be made up prior to final, inspection of equipment on roof pending. Water heater piping must be insulated. |
| 09/16/2024 |
COT - HCME - Mechanical Final |
|
Passed |
8/16/2024. All corrections were made. |