Inspection Status: Partial Pass
Inspection History: COT - HCME - Mechanical Progress
| Date |
Description |
Inspector |
Results |
Comments |
| 05/27/2026 |
COT - HCME - Mechanical Progress |
|
Partial Pass |
5-27-26: verified a 3" gas pipe located on east side stemming into building above ceiling under test at 15 psi. Pipe has been under test since yesterday- okay to continue with construction at progress areas. |
| 06/23/2026 |
COT - HCME - Mechanical Progress |
|
Canceled |
6-23-26: canceled |
| 06/24/2026 |
COT - HCME - Mechanical Progress |
|
Partial Pass |
6-24-26: 2" domestic copper lines above ceiling which extends from northwest wall of Suite 191 verified under test at 94 psi and 1/2" copper line (hose bib) located at west exterior wall of Suite 101 verified under test at 98 psi. Okay to continue with construction at progress areas. |