Inspection Status: Re-inspection required
Inspection History: COT - LCBU - Roof Nailing
| Date |
Description |
Inspector |
Results |
Comments |
| 05/14/2026 |
COT - LCBU - Roof Nailing |
|
Re-inspection required |
5-14-26: cs strap at post to beam, anchor bolts required within 12" at the end of each plate, tighten all anchor bolts, sheathing-cannot over penetrate more than 1/16" and nails cannot be closer than 3/8" from joints/edges, 12 nails required at each side of splice at shear wall/load bearing walls-see detail 35 for information. Roof nailing approved-okay to install crickets. Make corrections to parapet sheathing at east wall-gap between sheathing is larger than 1/2". Stopped inspection-additional items may be noted. |
| 05/19/2026 |
COT - LCBU - Roof Nailing |
|
Canceled |
5-19-26; canceled by contractor. Need to inspect parapet correction and installation of crickets. |
| 06/03/2026 |
COT - LCBU - Roof Nailing |
|
Passed |
|