Permit: TC-COM-0925-01779

Parcel: 141186020


Addresses:

10039 E OLD VAIL RD

Inspection Status: Re-inspection required

Inspection History: COT - LCBU - Roof Nailing 

Date Description Inspector Results Comments
05/14/2026 COT - LCBU - Roof Nailing  Re-inspection required 5-14-26: cs strap at post to beam, anchor bolts required within 12" at the end of each plate, tighten all anchor bolts, sheathing-cannot over penetrate more than 1/16" and nails cannot be closer than 3/8" from joints/edges, 12 nails required at each side of splice at shear wall/load bearing walls-see detail 35 for information. Roof nailing approved-okay to install crickets. Make corrections to parapet sheathing at east wall-gap between sheathing is larger than 1/2". Stopped inspection-additional items may be noted.
05/19/2026 COT - LCBU - Roof Nailing  Canceled 5-19-26; canceled by contractor. Need to inspect parapet correction and installation of crickets.
06/03/2026 COT - LCBU - Roof Nailing  Passed