Permit: TC-COM-0925-01779

Parcel: 141186020


Addresses:

10039 E OLD VAIL RD

Inspection Status: Partial Pass

Inspection History: COT - HCEL - Electrical Progress  

Date Description Inspector Results Comments
03/12/2026 COT - HCEL - Electrical Progress   Partial Pass 3-12-26: Building 3-verified trench depth on 4" schedule 40 communication riser, 2-2 1/2" schedule 40 conduits for p1, p2, p3 feeders, SES -4" schedule 40 conduits, 1 1/2 " panel hp-6-1" & 1-!/2"conduits, 3-1" conduits for pv chargers. Okay to backfill approximately 90' trench.
03/17/2026 COT - HCEL - Electrical Progress   Not Ready
03/27/2026 COT - HCEL - Electrical Progress   Partial Pass 3-27-26: verified trench depth at 2' for 2" electrical schedule 40 conduits at Building 3. Electrical conduits are for phone boards-okay to backfill progress areas
06/03/2026 COT - HCEL - Electrical Progress   Partial Pass 6/3/26: light pole reinforcement and electrical underground/ grounding approved at light poles (6,7,8,9,10,11,12), GROUNDING AT Service entrance approved.
06/23/2026 COT - HCEL - Electrical Progress   Canceled 6-23-26: canceled
06/24/2026 COT - HCEL - Electrical Progress   Partial Pass 6-24-26: partial pass for in wall rough electrical and lighting above ceiling at canopies. Secure mc cabling within 12" of box proximity, ground metal boxes above ceiling, and make sure that all receptacles contain grounding nut and pigtail.
06/30/2026 COT - HCEL - Electrical Progress   Partial Pass 6-30-26: fire foam through penetrations at exterior shear walls above doors and fire foam rigid conduit for exterior lighting.
07/02/2026 COT - HCEL - Electrical Progress   Partial Pass 7-2-26: see previous notes from 6/30/26.
07/07/2026 COT - HCEL - Electrical Progress   Partial Pass 7.7.26
Fire foamed all penetrations called out on 6/30/26.