Inspection Status: Partial Pass
Inspection History: COT - LCME - Mechanical Intermediate
| Date |
Description |
Inspector |
Results |
Comments |
| 05/05/2026 |
COT - LCME - Mechanical Intermediate |
|
Partial Pass |
5-5-26: warehouse mechanical intermediate verified per plans. Pending office areas. |
|
COT - LCME - Mechanical Intermediate |
|
Re-inspection required |
5-20-26: add supports to flex where resting on ceiling grid-supports are required within 4' of registers, insulate all ducting, complete flex tie ins to registers, tape all tears at ducts/trunks- this is required to avoid condensation build up. |
|
COT - LCME - Mechanical Intermediate |
|
Scheduled |
|