Inspection Status: Partial Pass
Inspection History: COT - LCEL - Electrical Above Ceiling
| Date |
Description |
Inspector |
Results |
Comments |
| 05/05/2026 |
COT - LCEL - Electrical Above Ceiling |
|
Partial Pass |
5-5-26: partial pass-pending a few above ceiling ceiling light tie-in's and labeling of junction boxes at "field operations room" and office space areas. |
| 05/20/2026 |
COT - LCEL - Electrical Above Ceiling |
|
Re-inspection required |
5-20-26: labeling junction at northeast section of office space areas, all electrical conduits must be individually supported and cannot be zip tied to existing wiring. The conduits must be supported by independent support wires, rods, or cables attached by the structural ceiling. See NEC 300.11 (B) for information. |
|
COT - LCEL - Electrical Above Ceiling |
|
Scheduled |
|