Permit: TC-COM-0925-01709

Parcel: 14026040C


Addresses:

2850 E DREXEL RD

Inspection Status: Partial Pass

Inspection History: COT - LCEL - Electrical Above Ceiling 

Date Description Inspector Results Comments
05/05/2026 COT - LCEL - Electrical Above Ceiling  Partial Pass 5-5-26: partial pass-pending a few above ceiling ceiling light tie-in's and labeling of junction boxes at "field operations room" and office space areas.
05/20/2026 COT - LCEL - Electrical Above Ceiling  Re-inspection required 5-20-26: labeling junction at northeast section of office space areas, all electrical conduits must be individually supported and cannot be zip tied to existing wiring. The conduits must be supported by independent support wires, rods, or cables attached by the structural ceiling. See NEC 300.11 (B) for information.
COT - LCEL - Electrical Above Ceiling  Scheduled