Inspection Status: Partial Pass
Inspection History: COT - HCBU - Interior Shear Bracing
| Date |
Description |
Inspector |
Results |
Comments |
| 06/25/2026 |
COT - HCBU - Interior Shear Bracing |
|
Partial Pass |
6-25-26: drywall screw inspection from GL: 1/D-F & 4/D-F approved for tape & texture. Also, verified framing along west wall approved. Add screws to east metal framing demising wall at stud to sill-east side of area 109. Make sure to schedule a plumbing intermediates inspection prior to covering wall- we need to verify supports at DWV and copper lines. |
| 07/01/2026 |
COT - HCBU - Interior Shear Bracing |
|
Partial Pass |
7-1-26: one-side drywall screw inspection at G/L: 3.5/ B-C is okay to tape & texture. |
| 07/08/2026 |
COT - HCBU - Interior Shear Bracing |
|
Partial Pass |
7/8/26: one-side drywall screw inspection at GL E-F/1-2 okay to tape and texture |
| 07/29/2026 |
COT - HCBU - Interior Shear Bracing |
|
Partial Pass |
7-29-26: drywall screw inspection at in walls of front offices, back of house restrooms, north side of demising wall at sales room & mother's room approved for tape & texture. |
| 07/30/2026 |
COT - HCBU - Interior Shear Bracing |
|
Partial Pass |
7-30-26: in wall drywall screw inspection at room 125 approved for tape & texture. Verified metal framing at "mother's room." Okay to proceed with const at progress areas. |
| 08/03/2026 |
COT - HCBU - Interior Shear Bracing |
|
Partial Pass |
8-3-26: in wall drywall screw inspection at Deli, break room, east side of vestibule and above ceiling hard lids at back of house restrooms. Okay to tape & texture progress areas. |
| 08/05/2026 |
COT - HCBU - Interior Shear Bracing |
|
Partial Pass |
8/5/2026 Partial pass. Vestibule (Entry way) drywall screw approved above headers to ceiling approved. |