Permit: TC-COM-0925-01634

Parcel: 14118602A


Addresses:

10015 E OLD VAIL RD

Inspection Status: Partial Pass

Inspection History: COT - HCPL - Plumbing Intermediate 

Date Description Inspector Results Comments
06/08/2026 COT - HCPL - Plumbing Intermediate  Partial Pass 6-8-26: 2- DWV at meat prep wall verified under test together with 2 domestic copper lines verified under test at 100 psi
07/16/2026 COT - HCPL - Plumbing Intermediate  Partial Pass 7-16-26: in wall/above ceiling DWV/ Copper water lines verified under test- (pex lines not verified) Copper lines at 100 psi. Verified supports & grommets at the bakery/deli room 109, meat cooler, break room, mother's room, public restrooms, 108, DWV at 118, restroom 128, 104, 103/102. Okay to continue with construction, however, we will have to verify insulation of hot/cold and hot water returns within the building- See P000 note 42. Also, insulate piping routed at exterior walls of building with 2" batt insulation See P000 Note 19 for information.
07/27/2026 COT - HCPL - Plumbing Intermediate  Partial Pass 7-27-26: verified pex lines at back of house all under test at 100 psi.