Permit: TC-COM-0925-01634

Parcel: 14118602A


Addresses:

10015 E OLD VAIL RD

Inspection Status: Partial Pass

Inspection History: BULD - Electrical Clearance

Date Description Inspector Results Comments
07/10/2026 BULD - Electrical Clearance Partial Pass 7.10.26
Partial pass, Pending secondary's.
07/21/2026 BULD - Electrical Clearance Re-inspection required 7-21-26: add duct sill at SES, quick connect and MDP. Install required labeling at SES per NEC requirements, and submit address correction to the city for review & approval. Will verify gas & water bonding at upcoming inspection.
07/29/2026 BULD - Electrical Clearance Re-inspection required 7-29-26: pending permanent labeling at SES together with gas/water bonding.
07/30/2026 BULD - Electrical Clearance Re-inspection required 7-30-26: bonding not ready.
07/31/2026 BULD - Electrical Clearance Partial Pass 7-31-26: partial pass pending address RFI approval by the city- okay to energize SES at 10015 E. Old Vail Rd. ECO clearance issued to TEP.