Inspection History Details
Inspection Status: Partial Pass
Inspection History: BULD - Electrical Clearance
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/10/2026 | BULD - Electrical Clearance | Partial Pass | 7.10.26 Partial pass, Pending secondary's. |
|
| 07/21/2026 | BULD - Electrical Clearance | Re-inspection required | 7-21-26: add duct sill at SES, quick connect and MDP. Install required labeling at SES per NEC requirements, and submit address correction to the city for review & approval. Will verify gas & water bonding at upcoming inspection. | |
| 07/29/2026 | BULD - Electrical Clearance | Re-inspection required | 7-29-26: pending permanent labeling at SES together with gas/water bonding. | |
| 07/30/2026 | BULD - Electrical Clearance | Re-inspection required | 7-30-26: bonding not ready. | |
| 07/31/2026 | BULD - Electrical Clearance | Partial Pass | 7-31-26: partial pass pending address RFI approval by the city- okay to energize SES at 10015 E. Old Vail Rd. ECO clearance issued to TEP. |