Inspection Status: Re-inspection required
Inspection History: COT - HCEL - Electrical Intermediate
| Date |
Description |
Inspector |
Results |
Comments |
| 07/17/2026 |
COT - HCEL - Electrical Intermediate |
|
Re-inspection required |
7-17-26: called poc at 758am but it went straight to voicemail. I then called another contractor from the site but received no answer. I waited on site for over 10 minutes and left at 810. Please reschedule when ready. |
| 07/20/2026 |
COT - HCEL - Electrical Intermediate |
|
Partial Pass |
7-20-26: in wall rough electrical room's 102, 101, 103, 104-add clamps at backing areas to secure conduit , 125, mothers room, 122, 108, deli-missing pigtail receptacle at southeast wall, 129, 126, 127, 128, stock area-119. Okay to continue with construction at progress areas and will verify required corrections at upcoming inspection. |
| 07/21/2026 |
COT - HCEL - Electrical Intermediate |
|
Partial Pass |
7-21-26: corrections made at in wall electrical. Okay to continue with consolidation at progress areas. |
| 07/24/2026 |
COT - HCEL - Electrical Intermediate |
|
Partial Pass |
7-24-26: Disregard previous notes- those were intended for a different job. Rough electrical above ceiling at back of house restrooms and office space areas in front approved. |
| 07/24/2026 |
COT - HCEL - Electrical Intermediate |
|
Re-inspection required |
7-24-26: excavation/ reinforcement on 5 light pole cages verified per plans. Remove all loose fill from bottom of trenches, install grounds, and we need to verify anchor bolts. |
| 08/03/2026 |
COT - HCEL - Electrical Intermediate |
|
Partial Pass |
8-3-26: partial pass at above ceiling electrical at sales areas. Install plastic bushings at junction boxes, add pigtails/ground screws and label all junction boxes. |
| 08/20/2026 |
COT - HCEL - Electrical Intermediate |
|
Partial Pass |
8/20/26: partial pass for above ceiling at sales area, properly secure emt (3' from box and 10' thereafter), all KOs must be sealed, provide spec sheet on light fixtures |