Inspection Status: Partial Pass

Inspection History: COT - LCEL - Electrical Underground 

Date Description Inspector Results Comments
03/11/2026 COT - LCEL - Electrical Underground  Partial Pass 3/11/26: UFER APPROVED
07/02/2026 COT - LCEL - Electrical Underground  Partial Pass 7-2-26: verified trench depth at 43" on a 4" Schedule Conduit from TEP transformer to building intended for main panel. Okay to backfill approximately 190' of trench using shading materials.