Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - HCPL - Sewer
Permit Number - TC-COM-0923-02246
Inspection Description - COT - HCPL - Sewer
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2025 | COT - HCPL - Sewer | Partial Pass | Partial pass. Approximately 120' in place. Okay to backfill progress areas. Shading material is required. Once completed pressure test is required. Verify tape is in place also. 7/31/2025 | |
| 08/04/2025 | COT - HCPL - Sewer | Partial Pass | Partial pass. Approximately 120' in place. Okay to backfill progress areas. Shading material is required. Once completed pressure test is required. Verify tape is in place also. 7/31/2025 8/4/25: 30' in place. Ok to backfill progress areas. Shading material required. |
|
| 08/06/2025 | COT - HCPL - Sewer | Partial Pass | Sewer line running north and south. With Wye branching off to catch grease interceptor. Approximately 25’. Three clean outs stubbed up. 8/6/2025 | |
| 08/07/2025 | COT - HCPL - Sewer | Not Ready | ||
| 08/08/2025 | COT - HCPL - Sewer | Partial Pass | 8-8-25: verified 6" SDR35 PVC sewer line and tracer wire-Okay to backfill open trench of approximately 25'. Air test will be performed at a later date. | |
| 08/11/2025 | COT - HCPL - Sewer | Passed | 8-11-25: sewer pressure test at 4 psi approved. Okay to continue with construction. |