Inspection Status: Passed
Inspection History: PDSD Engineering Division Pre-Construction SITE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/06/2026 |
PDSD Engineering Division Pre-Construction SITE |
|
Passed |
I met with the Project manager Robert Malin and the concrete subcontractor. They needed confirmation their intention and plan to build a compliant ramp was correct in regard to slope and matching existing concrete to the new concrete. I told them the new concrete ramp and landings poured will need to not exceed 2% crosslope. Where the landing meets the existing adjacent concrete there can be a transition area where it warps to meet the existing. Most of the warp should happen underneath the dog ear at the end of the handrail. Pouring an additional landing area for turning 180 degrees at end of ramp would not be necessary. It would be cost prohibitive due to existing conditions and would call for pouring new curb as well. Schedule sidewalk inspection before pouring ramp and landings. |