Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - LCEL - Electrical Intermediate
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/14/2026 | COT - LCEL - Electrical Intermediate | Partial Pass | 4-14-26: in wall/above ceiling electrical rough-in approved. Fire caulk all penetrations at top plates. Note: Smoke detector on Egress plan shows smoky in back hallway near restroom rather than directly inside of restroom. See egress plan and relocate. We will inspect penetrations prior to covering of any walls. Okay to continue with construction at progress areas. |
|
| 07/20/2026 | COT - LCEL - Electrical Intermediate | Re-inspection required | 7-20-26: missing knockouts at panel, missing panel schedules, add covers to all light receptacles, missing smoke and heat detectors-see plans for details, back restroom receptacle must be gfci, provide ladder for roof access, install all equipment.Stopped inspection-additional items may be noted. | |
| 08/13/2026 | COT - LCEL - Electrical Intermediate | Passed |