Inspection History: COT - LCEL - Electrical Final 

Date Description Inspector Results Comments
02/19/2026 COT - LCEL - Electrical Final  Re-inspection required 2-19-26: install a gfci receptacle adjacent to water heater, disconnect must contain a permanent label, add permanent label to panel L1, provide permanent disconnect labels at rooftop-see NEC requirements for more information, install a weather resistant gfci receptacle together with a bubble cover at rooftop, secure whips on rooftop to where they are not lying directly on roof, provide a UL listed condenser pad at rooftop, missing light fixture at exterior back door
02/26/2026 COT - LCEL - Electrical Final  Passed