Inspection Status: Partial Pass
Inspection History: COT - LCEL - Grounding/Bonding
| Date |
Description |
Inspector |
Results |
Comments |
| 03/03/2026 |
COT - LCEL - Grounding/Bonding |
|
Partial Pass |
3-3-26: per revision-verified trench depth on 4-2 1/2" Schedule 40 conduits for switchgear together with 6" Schedule 40 conduits for transformer. 3/0 AWG grounded to building structure & 3/0 AWG for SES. Okay to backfill progress areas & pour SES Pad. If revision has not been submitted to the city for review/approval then please submit as an attachment. |
| 04/10/2026 |
COT - LCEL - Grounding/Bonding |
|
Not Ready |
4-10-26: grounding/bondng at SES not ready. |
| 05/05/2026 |
COT - LCEL - Grounding/Bonding |
|
Partial Pass |
5-5-26: verified 2 grounding rods with #4 copper for DCM. Okay to backfill progress areas. |
| 06/05/2026 |
COT - LCEL - Grounding/Bonding |
|
Passed |
6-5-26: grounding/bonding approved. |