Permit: TC-COM-0825-01478

Parcel: 140270490


Addresses:

2884 E GANLEY RD

Inspection Status: Partial Pass

Inspection History: COT - LCEL - Electrical Final 

Date Description Inspector Results Comments
06/08/2026 COT - LCEL - Electrical Final  Partial Pass 6-8-26: missing knockouts on 2 above ceiling junction boxes at warehouse, missing junction cover box/label adjacent to disconnect HEQ1, write " spare" to junction box at southwest wall of warehouse, missing knockout at wall junction box south west side of warehouse, update panel schedule for H2, Submit an updated panel schedule for LEQ2, gfci receptacle required west wall of break room, install weather resistant gfci & bubble cover at east wall for condensers.
06/09/2026 COT - LCEL - Electrical Final  Passed 6-9-26: electrical final approved.