Inspection Status: Re-inspection required
Inspection History: BULD - Electrical Clearance
Permit Number - TC-COM-0823-01920
Inspection Description - BULD - Electrical Clearance
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/19/2025 | BULD - Electrical Clearance | Re-inspection required | Failed - 400A 3-phase not per approved plan (600A) also wrong grounding conductor size installed, min #2/0 cu required | |
| 04/24/2025 | BULD - Electrical Clearance | Passed | Approved new 600A service panel and EV Charger installation - ECO Clearance to TEP is required | |
| 09/19/2024 | BULD - Electrical Clearance | Canceled | NR, 3-phase conductors not installed to transformer - cancelled by contractor |