Inspection Status: Re-inspection required
Inspection History: COT - LCEL - Electrical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 02/19/2025 |
COT - LCEL - Electrical Final |
|
Re-inspection required |
Failed - 400A 3-phase not per approved plan (600A) also wrong grounding conductor size installed, min #2/0 cu required |
| 04/24/2025 |
COT - LCEL - Electrical Final |
|
Passed |
|