Inspection Status: Not Ready

Inspection History: COT - LCME - Mechanical Intermediate

Date Description Inspector Results Comments
08/20/2026 COT - LCME - Mechanical Intermediate Not Ready 8/20/2026 provide proper fuse sizes. Label disconnect. Level out unit and secure to pad. Condensation line shall be protected and ran to roof drains. Properly insulate and protect line sets per C403.12.3.1. Provide spec sheets on condensation pump.