Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Requested
Inspection History: COT - LCME - Mechanical Final
| Date |
Description |
Inspector |
Results |
Comments |
|
COT - LCME - Mechanical Final |
|
Requested |
|
| 08/20/2026 |
COT - LCME - Mechanical Final |
|
Not Ready |
8/20/2026 provide proper fuse sizes. Label disconnect. Level out unit and secure to pad. Condensation line shall be protected and ran to roof drains. Properly insulate and protect line sets per C403.12.3.1. Provide spec sheets on condensation pump. |