Permit: TC-COM-0725-01347

Parcel: 13338005F


Addresses:

5 S HOUGHTON RD

Inspection Status: Partial Pass

Inspection History: COT - LCPL - Plumbing Final 

Date Description Inspector Results Comments
09/03/2026 COT - LCPL - Plumbing Final  Partial Pass 9/3/26: Provide labels at the discount area and raceway supports,
Install covers and WR-rated switches at the entry canopy,
Adjust mirror height so that it does not exceed 40 inches,
Provide the panel schedule in the manager’s office,
Provide GFCI protection at all wet/damp locations as required,
Install cover plates on all junction boxes (J-boxes) where required,
Label all disconnect boxes,
Repair or replace the dead receptacle located in the attic,
Paint exterior PVC conduit to match the required finish,
Secure the flexible electrical whip at the vacuum pump room on the roof,
Replace undersized HVAC fuses with properly sized fuses in accordance with the equipment requirements,
Properly install and secure the liquid-tight fitting at the rooftop exhaust connection, pending water sterilization report, okay to request extension of level 1 TCO
09/08/2026 COT - LCPL - Plumbing Final  Re-inspection required All field work complete; need to clear conditions.